Multi-signal Acquisition and Remote Monitoring
Connect instruments and I/O for local monitoring, send data over the wired uplink, and use the selected cellular service for failover. The drawing shows an example configured with 4G.
Front indicators, SIM slots, SMB antenna connections and rack mounting ears.
The photo shows a DC 110 V unit. Confirm the supplied power terminals and the assigned I/O and serial connections before wiring.
440 × 199 × 44 mm body. Approximately 485 × 200 × 45 mm with mounting ears and 2.27 kg.
| Standard | Signal | Standards |
|---|---|---|
| RS-232 | RXD, TXD, GND | EIA/TIA-232(ITU-T V.28) |
| RS-422 | TxD+, TxD−, RxD+, RxD− | EIA/TIA-422(ITU-T V.11) |
| RS-485 four-wire | TxD+, TxD−, RxD+, RxD− | EIA/TIA-485 |
| RS-485 two-wire | A(TX+), B(TX−), GND | EIA/TIA-485 |
| Item | Specification |
|---|---|
| Input Power Supply | Optional: AC 220 V, DC −48 V, DC 24 V, or DC 110 V. |
| Dual power supply combination | Optional: AC+AC, AC+DC, or DC+DC. |
| Item | Specification |
|---|---|
| Processing platform | Industrial processor running OpenWrt. |
| Electrical Ethernet | 4 × RJ45, 10/100/1000BASE-T auto-negotiation, full/half-duplex adaptation, supports Auto MDI/MDIX. The MAC address table can learn 4096 addresses. |
| Serial Port | 1–8 channels configurable. Each channel supports RS-232/RS-422/RS-485; three-in-one interface type can be configured via Web. |
| I/O resources | Up to 64 DI/DO/AI/AO channels, configured in groups of 2. Serial ports and I/O can be configured simultaneously. |
| Installation and Heat Dissipation | 19-inch rack mount, fanless. Physical dimensions: 440 × 199 × 44 mm, approximately 2.27 kg. With mounting ears, dimensions are approximately 485 × 200 × 45 mm (width × depth × height). |
| Environment | Operating and storage temperatures: −40–+85 °C; operating humidity: 0%–95% RH, no condensation. RedCap cellular module operates at −35–+75 °C; expansion range: −40–+85 °C; overall applicable range is confirmed on order. |
| Reliability | MTBF >100,000 hours, with watchdog and system monitoring protection. |
| Item | Parameters | Technical Specifications |
|---|---|---|
| Channel configuration | Up to 64 channels, configured in groups of 2, can combine DI, DO, current-type or voltage-type AI/AO. | |
| Digital input DI | Supports dry contact, NPN/PNP transistor wet contact, or pulse input. | |
| Digital output DO | Dry contact · output form | Signal relay |
| Dry contact · rated load | 30 VDC/2 A | |
| Dry contact · maximum switching frequency | 50 Hz | |
| dry contact · response time | <1.2 ms | |
| dry contact · surge protection | none | |
| wet contact · output mode | optical MOS relay / pulse output | |
| wet contact · rated load | 245 VDC/0.12 A | |
| wet contact · output level | 0–VCC (VCC is the power supply voltage of the device) | |
| Wet contact · Response time | <0.6 ms | |
| Wet contact · Surge protection | TVS + solid discharge tube | |
| Current input/output | Range | 0–20 mA (including 4–20 mA) |
| Resolution | 12 bits | |
| Sampling rate | 20,000 times/s | |
| Delay | <0.1 ms | |
| Normal temperature accuracy | 0.2% | |
| Input resistance | 125 Ω | |
| Output load capability | 600 Ω | |
| Voltage input/output | Range | 0–10 V (including 0–5 V) or −5–+5 V |
| Resolution | 12 bits | |
| Sampling rate | 20,000 times/s | |
| Delay | <1 ms | |
| Normal temperature accuracy | 0.2% | |
| Input resistance | 100 kΩ | |
| Output load capability | 600 Ω | |
| Item | Specification |
|---|---|
| Basic protocol | TCP, UDP, ARP, ICMP, HTTP, DNS, DHCP, SNMP, Telnet, SSH. Supports cross-gateway/cross-routing and automatic connection recovery after network interruption. |
| Data access | Modbus TCP Server, standard TCP/IP Socket. TCP supports multiple connections; UDP supports single-machine or multi-machine communication. |
| Digital control management | Supports SNMP Get/Set, used for reading inputs, reading or setting output states. Supports via touch screen, PLC local control or display. |
| Serial Port Networking | Supports Modbus RTU to Modbus TCP, SSL serial data encryption, MQTT multi-topic publishing and subscription, and transparent transmission. |
| JSON and cloud integration | Supports Modbus to JSON, parsing of JSON sent by the server and scheduled reporting. Can connect to Huawei Cloud, Alibaba Cloud, and Mobile Cloud via MQTT. |
| Configuration and Upgrade | Windows configuration tool, SSH, Telnet, Web and SNMP management, supports access control, quick configuration, local and remote firmware upgrade. |
| Wired Connection | LAN supports ARP, Ethernet, STP. WAN supports static IP, DHCP, PPPoE, PPTP, L2TP. |
| Item | Specifications or technical requirements | Description |
|---|---|---|
| Digital interface | Differential mode 6 kV, common mode 6 kV | Reduce the impact of induced high voltage and switch operation surges on the signal circuit. |
| Serial interface | Differential mode 6 kV, common mode 6 kV | Used for surge protection of serial line transmission. |
| Ethernet interface (RJ45) | 4 kV | Reduce the risk of transient overvoltage transmitted through network cables. |
| Digital and serial interface test basis: IEC 61000-4-5, open-circuit voltage waveform 10/700 μs, test source impedance 40 Ω. | ||
| Item | Specification |
|---|---|
| Function | 1 LoRa data access channel, forwarding received LoRa data to the network. |
| Radio Frequency | Available from 400–520 MHz, default is 490 MHz. Default transmission power is 20 dBm (100 mW). |
| Air interface | 0.018–37.5 kbps, nominal reception sensitivity can reach −139 dBm. |
| Typical range | 4–8 km, actual performance depends on terrain, antenna, site interference, and local regulations. |
| Antenna interface | SMA, internal pin with external thread. |
| Item | Specification |
|---|---|
| 4G Cat.4 | LTE FDD/TDD, 3GPP Rel-9, no carrier aggregation. Theoretical peak of the module: FDD downlink/uplink 150/50 Mbps, TDD 130/30 Mbps. |
| 5G RedCap | 3GPP Rel-17 RedCap, Sub-6 GHz, supports 5G NR SA and LTE Cat.4 fallback. Theoretical peak of the module: 5G SA downlink/uplink 226/120 Mbps; LTE downlink/uplink 150/50 Mbps, actual performance depends on network configuration. |
| Connection and Authentication | Supports APN and VPDN, compatible with IoT cards, regular mobile cards, and dedicated cards. Supports CHAP, PAP, MS-CHAP, MS-CHAPv2, or no authentication. |
| Dual SIM and Switching | 2 SIM card slots, dual SIM single standby, supports eSIM (requires operator activation). Can switch operators according to configuration, using one cellular connection at a time. The front panel has 2 SMB antenna ports, with connections based on selected antenna configuration. |
| Link Failover | After the wired link fails, it can switch to cellular, with automatic detection of wired recovery. Switching and recovery time are affected by the on-site network and configuration. |
| Standard | -CN | -AU | -EU |
|---|---|---|---|
| Region | China / India | Latin America/Australia/New Zealand | EMEA / Southeast Asia |
| LTE-FDD | B1/3/5/8 | B1/2/3/4/5/7/8/28/66 | B1/3/5/7/8/20/28 |
| LTE-TDD | B34/38/39/40/41 | B40 | B38/40/41 |
| WCDMA | B1/5/8 | B1/2/4/5/8 | B1/5/8 |
| GSM | EGSM900/DCS1800 | GSM850/EGSM900/DCS1800/PCS1900 | EGSM900/DCS1800 |
| Standard | -CN | -EU |
|---|---|---|
| Region | China | EMEA/Southeast Asia/Australia/New Zealand |
| 5G NR SA | n1/3/5/8/28/40/41/78/79 | n1/3/5/7/8/20/28/38/40/41/77/78 |
| LTE-FDD | B1/3/5/8 | B1/3/5/7/8/20/28 |
| LTE-TDD | B34/38/39/40/41 | B38/40/41/42/43 |
EMEA refers to Europe, the Middle East, and Africa. The frequency band, operator, and on-site coverage at the installation location must be verified before connection. The cellular antenna solution and RedCap expansion temperature conditions are confirmed according to the order.
Connect instruments and I/O for local monitoring, send data over the wired uplink, and use the selected cellular service for failover. The drawing shows an example configured with 4G.
Choose up to eight serial ports and 64 I/O channels. I/O choices advance in pairs. Power, LoRa settings and signal ranges are specified with the order.
FCT-6700-G4 / Interface code + quantity / UF or UR / Region
| NO | Name | Definition |
|---|---|---|
| 01 | FC / T | FC stands for Feichang; T stands for industrial gateway. |
| 02 | 6700 | 19-inch rack series. |
| 03 | G4 | 4-channel Gigabit RJ45 copper Ethernet ports. |
| 04 | D/R/X/S | Represent RS-485, RS-232, RS-422, or selectable RS-232/422/485 serial port respectively. The configuration quantity shall not exceed 8. |
| 05 | K/J | K stands for DI; J stands for DO. Configured in groups of 2 channels. |
| 06 | A/M/V/Y | A stands for current input; M stands for current output; V stands for voltage input; Y stands for voltage output. The total number of channels with DI/DO shall not exceed 64. |
| 07 | Cell and region | UF is 4G Cat.4 (-CN, -AU, -EU); UR is 5G RedCap (-CN, -EU); choose one. The region suffix is placed at the end. |
| Model | Configuration |
|---|---|
| FCT-6700-G4-CN | Official website: abbreviated version of 4G Cat.4 for China; serial ports, I/O, and other options shall be specified in the order. |
| FCT-6700-G4S8K16J16A16M16UF-CN | 8-channel three-in-one serial port + 16 DI + 16 DO + 16 current AI + 16 current AO, 4G Cat.4 Chinese version. |
| FCT-6700-G4S8K16J16V16Y16UR-EU | 8-channel three-in-one serial port + 16 DI + 16 DO + 16 voltage AI + 16 voltage AO, 5G RedCap European region configuration. |
The order shall specify serial port format and channels, number of various I/O channels, range and input/output types, cell version and region, LoRa configuration, power input, and single/double power combinations.