How CAN Bus Fiber Optic Modems Extend Fieldbus: Differential Signals, Arbitration Timing, and Selection
Review CAN arbitration timing, extension methods and bus behavior.
Group 1 is the CAN bus. Group 2 provides the separate RS-485 configuration port. F1 and F2 are the two optical ports.
PWR1 and PWR2 are redundant 9–70 V DC inputs. Match the marked V1−, V1+, V2− and V2+ terminals and use the protective earth stud.
Use the 35 mm DIN-rail clip or the wall-mounting holes. Check clearances for the selected optical connector and its cable bend radius.
| Group | Marking | Connection |
|---|---|---|
| CAN service | Group 1 | CAN-H / CAN-L / signal ground. Built-in 120 Ω resistor. Check the delivered markings and bus termination. |
| RS-485 setup | Group 2 | Set CAN bit rate and other device parameters using the configuration software. |
| Fiber | F1 / F2 | Match the ordered optic. Cross TX and RX on dual-fiber links, and pair complementary wavelengths on single-fiber links. |
| Dual DC | PWR1 / PWR2 | Redundant DC 9–70 V. Match V1− / V1+ and V2− / V2+ to their markings. |
| Protective earth | Earth stud | Connect protective earth per site requirements. |
110 × 82 × 40 mm for the FC-port version shown. Verify the ordered connector version and allow cable clearance.
| Item | Specification |
|---|---|
| CAN interface | One CAN bus, CAN-H / CAN-L / signal ground with built-in 120 Ω resistance. |
| CAN bit rate | 10 kbit/s to 1 Mbit/s. Set through the RS-485 setup port and software. |
| Configuration port | One RS-485 channel for parameter setup. |
| Optical interfaces | Two, marked F1 and F2. FC, SC, ST or LC by order. Single- or dual-fiber; match the equipment at the other end. |
| Optical reach per link | 20 km standard single-mode, up to 120 km custom single-mode, or 2 km multimode option. Confirm the optical link budget. |
| Network topology | Point-to-point, chain, star or ring. In a closed ring, a single link failure triggers automatic communication recovery. |
| Power input | Dual redundant DC 9–70 V. |
| Enclosure and mounting | Anodized aluminum, fanless, IP40. 110 × 82 × 40 mm for the FC version. 35 mm DIN rail or wall mounting. |
| Operating temperature | −40 to +85 °C. |
| Interface | Rating or test condition | Protection |
|---|---|---|
| CAN service interface | 6 kV open-circuit peak | CAN line surge protection. |
| Additional CAN protection | 600 W surge per line; ±15 kV ESD | Self-restoring overcurrent protection. |
Surge immunity tested to GB/T 17626.5 / IEC 61000-4-5 with a 10/700 μs open-circuit waveform and 40 Ω source impedance.
Link each station’s F2 to the next station’s F1 and connect the final station back to the first. With the closed ring operating, a single link break leaves an alternate path. Verify CAN protocol and bit rate compatibility before deployment.
Link each station’s F2 to the next station’s F1. Leave F1 at the first station and F2 at the last station open. In the drawing, [1] marks the fiber link to the later stations, [2] and [3] mark the open end ports, and [4] marks each local CAN connection.
Specify the connector (FC, SC, ST or LC), single or dual fiber, optical mode, link reach, equipment at the other end, topology and CAN bit rate. Confirm mounting and cabling accessories with the order.
| Ordering Model | Configuration |
|---|---|
| FCP-1300-C1-RI | One CAN channel, two optical ports, RS-485 configuration and dual DC 9–70 V. Standard single-mode reach is 20 km. |
| Segment | Definition |
|---|---|
| FCP-1300 | Product series. |
| C1 | One CAN bus channel. |
| RI | Ring-network model suffix. |
One per unit, through Group 1 (CAN-H, CAN-L and signal ground). Use Group 2 and the configuration software to set the CAN bit rate.
10 kbit/s to 1 Mbit/s. Set the same compatible rate and verify that the connected equipment uses a compatible CAN protocol.
A closed ring provides a second path and restores communication after one link fails. An open daisy chain has no return path.
The rating is per optical span between adjacent stations. The standard single-mode reach is 20 km. The optional optics have different reach limits and must match the site link budgets.
Use the marked terminals for dual redundant DC 9–70 V input. Fit the 35 mm DIN-rail clip or use the wall-mounting holes.
Review CAN arbitration timing, extension methods and bus behavior.
Check protocol, topology and acceptance with the connected equipment.
Compare ring, chain and backup connections for distributed sites.
Tell us your application, quantity and preferred configuration.