1-to-4 4–20 mA Signal Splitter

Model:FC-A4JM
3 +3

Share one 4–20 mA measurement with four devices

  • Send one measurement to four receiversDistribute one 4–20 mA input to four isolated loops for controllers, displays or drives.
  • Keep loop references separateEach output has its own return. The input, outputs and supply are isolated, with a specified withstand voltage of at least 1,500 V DC for one minute.
  • Install in a control cabinetUse a separate 24 V DC supply and mount the unit on 35 mm DIN rail or a wall.

Purpose & Applications

  • Send the same pressure or flow measurement from one transmitter to four receivers.
  • Use the isolated outputs with separate loop references. Wire a two-, three- or four-wire transmitter according to its power and signal arrangement.
  • Power the splitter separately at 24 V DC. The unit is for general industrial applications. Intrinsically safe hazardous-area installations require suitable certified equipment.

Key Features

Signal performance
2,000 samples/s, latency below 0.1 ms and 0.1% room-temperature accuracy.
Output loading
600 Ω maximum load per output and 125 Ω input resistance.
Isolation and protection
Transformer isolation and separate analog grounds. The datasheet specifies 6 kV protection at the analog and power interfaces.
Mounting and environment
101 × 114 × 23 mm, 35 mm DIN rail or wall mounting, and −40 to +85 °C operation.

Terminals & Wiring
InterfaceMarkingsConnection
Outputs 3 and 4O3+ / G3 / O4+ / G4Top row. Connect receivers 3 and 4 to their respective positive and return terminals.
Outputs 1 and 2O1+ / G1 / O2+ / G2Second row. Connect receivers 1 and 2 to their respective positive and return terminals.
Input and sensor feedIN+ / G / 24V / GOne 4–20 mA input. Use the sensor feed as shown for the transmitter wiring.
Separate powerV+ / V− / V− / NCConnect a separate 24 V DC supply. Leave NC unconnected.
Connection TypeWiring
Two-wire transmitterConnect input-side 24V to transmitter VCC and the transmitter signal to IN+. Leave both input G terminals unconnected.
Three-wire transmitterConnect 24V and G to transmitter VCC and GND, and the transmitter signal to IN+.
Four-wire transmitterConnect 24V and G to transmitter VCC and power GND, signal GND to input G, and the transmitter signal to IN+.
Four output loopsConnect each On+ and Gn to the corresponding receiver + and − terminals (n = 1–4). Match each receiver to 4–20 mA.

Keep the input and output references and the device supply negative separate. Check sensor-feed capacity against the transmitter load.

Dimensions & Mounting

101 × 114 × 23 mm. Refer to the six-view drawing for enclosure and mounting clearances.

Analog Signal
ItemSpecification
SignalOne isolated 4–20 mA input and four isolated 4–20 mA outputs.
Sampling rate2,000 samples/s
Latency<0.1 ms
Maximum load600 Ω per output
Input resistance125 Ω
Accuracy0.1% at room temperature
Power & Isolation
ItemSpecification
SupplySeparate 24 V DC supply, 50 mA maximum at 24 V.
Isolation methodTransformer isolation. The input, four output loops and supply have separate references.
Dielectric withstandAt least 1,500 V DC for one minute between input/output, input/power and output/power.
Analog protection6 kV per analog channel against induced transients, per datasheet.
Power protection6 kV at the power input. Includes overload and reverse-polarity protection.
EMCIndustrial EMC level 4 requirements per datasheet.
Environment & Mounting
ItemSpecification
Operating and storage−40 to +85 °C
Humidity0–95% RH, non-condensing
Cooling and screeningFanless, 100% burn-in testing. MTBF >100,000 hours.
Installation and dimensions35 mm DIN rail or wall mounting. Enclosure 101 × 114 × 23 mm.

Distribute one measurement to four devices

Connect the two-wire transmitter to input-side 24V and IN+. Leave both input G terminals open. Each receiving instrument uses its own 4–20 mA output and return.

Order the FC-A4JM

Confirm the transmitter wiring, the load on each of the four receivers and the mounting method. FC-A4JM has one input and four isolated outputs.

Ordering Model
Ordering ModelConfiguration
FC-A4JMOne isolated 4–20 mA input, four isolated 4–20 mA outputs and a dedicated 24 V DC power terminal.

Input and outputs

2 questions
01QCan all four outputs carry the same measurement?
A

Yes. One 4–20 mA input feeds four isolated outputs. Each output has a separate return terminal.

02QHow do I wire a two-wire transmitter?
A

Connect input-side 24V to transmitter VCC and the transmitter signal to IN+. Leave both input G terminals unconnected.

Isolation and load

2 questions
03QCan I join the output grounds?
A

Keep G1 through G4 separate from each other, input G and supply V− to maintain the isolated loop references.

04QWhat is the maximum load per output?
A

The specified maximum is 600 Ω for each output. Check the load on each receiver loop.

Power and mounting

1 question
05QDoes the splitter need its own supply?
A

Yes. Apply a separate 24 V DC supply to the marked V+ and V− terminals. Leave NC unconnected.

Signal Interface Overview

InterfaceFunction
Input1 × 4–20 mA
Outputs4 × isolated 4–20 mA
Supply24 V DC