How RS485 Hubs Work: Segmentation, Termination and Polling
Check termination and polling when adding a repeater or hub to an RS-485 network.
Match D0 to A0/B0/G0, each branch to its A/B pair and the DC supply to V+/V−. R0 handles uplink termination. SPD selects the filter mode.
Clip onto a 35 mm DIN rail. Leave clearance for signal terminals, power wiring and the clip.
| Interface | Markings | Connection |
|---|---|---|
| D0 uplink | A0 / B0 / G0 | Connect the PLC or upstream bus. A0 is positive, B0 is negative and G0 is the uplink reference ground. |
| D1 branch | A1 / B1 | Two-wire RS-485 branch 1. |
| D2 branch | A2 / B2 | Two-wire RS-485 branch 2. |
| D3 branch | A3 / B3 | Two-wire RS-485 branch 3. |
| D4 branch | A4 / B4 | Two-wire RS-485 branch 4. |
| Power | V+ / V− | DC 9–70 V. Connect the positive supply to V+ and its negative to V−. Four-position, 5.08 mm-pitch terminal group. |
| Termination and filtering | R0 / SPD | R0 is associated with the built-in 120 Ω uplink termination. Leave SPD open for normal operation. Connect SPD to V− for strong FPGA filtering. |
114 × 101 × 23 mm. Approximately 0.19 kg. Install on a 35 mm DIN rail.
| Item | Specification |
|---|---|
| RS-485 interface | One EIA/TIA-485 uplink and four isolated EIA/TIA-485 branches. Two-wire A (+) and B (−), with automatic transmit/receive switching. |
| Normal filtering | SPD open. Maximum 256 kbps. |
| Strong filtering | Connect SPD to V−. The FPGA uses stronger digital filtering, with a maximum of 38.4 kbps. |
| Loading and distance | Up to 128 enhanced nodes per port. Maximum 2,200 m at 9,600 bps under suitable wiring conditions. |
| Item | Rating | Conditions |
|---|---|---|
| RS-485 circuits | 6 kV surge per port | Three-stage surge protection for five channels. |
| Power supply input | 6 kV surge | Protects against transients on the supply line. |
| Signal and power isolation | 3 kV | High-speed optocouplers and isolated DC–DC power. The five port grounds are isolated from each other and the supply ground. |
| AC misconnection fault | 220 / 380 V AC fault condition | The isolation is intended to protect devices on other ports if a line is miswired. The affected port may be damaged. |
RS-485 surge test: GB/T 17626.5 / IEC 61000-4-5, 10/700 μs open-circuit waveform and 40 Ω source impedance.
| Status | PWR/D0 | D1–D4 |
|---|---|---|
| Steady green | Power is on. | — |
| Flashing green | Data received at D0. | Data received on that branch. |
| Flashing red | A/B short circuit at D0. | A/B short circuit on that branch. |
| Steady red | Abnormal continuous-zero data at D0. | Abnormal continuous-zero data on that branch. |
| Off | Power is off. | No received data on that branch. |
Continuous-low detection compares the received low level with the maximum continuous-zero duration at 300 bps. The hub isolates the abnormal channel and lights its indicator.
| Item | Specification |
|---|---|
| Supply and consumption | DC 9–70 V, under 1 W. Overload and reverse-polarity protection. |
| Structure and mounting | Fanless 35 mm DIN-rail housing, approximately 0.19 kg. |
| Environment | Operating and storage −40 to +85 °C. Operating humidity 0–95% RH, non-condensing. |
| Reliability | MTBF above 200,000 hours, 100% burn-in testing and industrial Level 4 EMC per V1.5. |
Connect the PLC to D0 and the field devices to D1–D4. If branch 3 has a fault, the hub isolates it while healthy branches keep communicating.
The diagram shows common-mode and FPGA filtering, per-channel isolation and automatic forwarding control. G1–G4 are internal. Connect each branch through its A/B pair.
Specify quantity, the DC supply, cable and mounting accessories with the order.
| Ordering Model | Configuration |
|---|---|
| FCC-1210-D1D4 | One RS-485 uplink, four isolated RS-485 branches, 3 kV isolation, 6 kV surge protection and 9–70 V DC power. |
| Segment | Definition |
|---|---|
| FCC / 1210 | Product prefix and modular DIN-rail series. |
| D1 | One uplink on D0. |
| D4 | Four isolated RS-485 branches, D1–D4. |
Connect the controller to A0/B0 and its reference ground to G0. Connect field devices to the A/B pairs of D1–D4.
The branches expose A and B. Their internal electrical grounds are isolated from the other ports and the power ground.
Use this setting for strong FPGA filtering when electrical noise affects reception. The maximum rate is 38.4 kbps in this mode and 256 kbps with SPD open.
Flashing red indicates an A/B short on that branch. Steady red indicates abnormal continuous-zero data.
Connect 9–70 V DC to V+ and V− with the marked polarity. Use a 35 mm DIN rail and reserve clearance for cables.