Smart 4-Port RS-485 DIN-Rail Isolated Hub

Model:FCC-1210-D1D4
3,387 +0

Connect one RS-485 bus to four isolated branches

  • Connect one controller to four branchesConnect the PLC or upstream RS-485 bus to D0. Connect the four field branches to D1–D4.
  • Keep other branches running when one failsThe hub automatically isolates a branch that has a short circuit or sends abnormal continuous-zero data. Use the branch LED to locate the fault.
  • Choose a filter setting for the siteLeave SPD open for up to 256 kbps. Connect SPD to V− for strong FPGA filtering at up to 38.4 kbps.

Purpose & Applications

  • Expand one two-wire RS-485 bus into four independently isolated field branches for instruments, sensors and other devices.
  • Common-mode chokes and FPGA digital filtering suppress interference and glitches. Strong filtering trades maximum baud rate for improved noise rejection.
  • The hub detects abnormal data and shorts by branch. The affected branch can be isolated while the other three keep communicating.

Key Features

Per-port settings
Set baud rate, parity, data bits and stop bits per port. Supports configuration software and Modbus RTU settings.
Branch isolation
The five RS-485 grounds and supply ground are isolated. Each distribution port exposes only A/B.
Protection
6 kV surge rating per RS-485 channel and for the power input.
Panel status
PWR/D0 reports power and hub activity. D1–D4 report the corresponding distribution ports.

Terminals & Wiring
InterfaceMarkingsConnection
D0 uplinkA0 / B0 / G0Connect the PLC or upstream bus. A0 is positive, B0 is negative and G0 is the uplink reference ground.
D1 branchA1 / B1Two-wire RS-485 branch 1.
D2 branchA2 / B2Two-wire RS-485 branch 2.
D3 branchA3 / B3Two-wire RS-485 branch 3.
D4 branchA4 / B4Two-wire RS-485 branch 4.
PowerV+ / V−DC 9–70 V. Connect the positive supply to V+ and its negative to V−. Four-position, 5.08 mm-pitch terminal group.
Termination and filteringR0 / SPDR0 is associated with the built-in 120 Ω uplink termination. Leave SPD open for normal operation. Connect SPD to V− for strong FPGA filtering.
Dimensions & Mounting

114 × 101 × 23 mm. Approximately 0.19 kg. Install on a 35 mm DIN rail.

Communication & Filtering
ItemSpecification
RS-485 interfaceOne EIA/TIA-485 uplink and four isolated EIA/TIA-485 branches. Two-wire A (+) and B (−), with automatic transmit/receive switching.
Normal filteringSPD open. Maximum 256 kbps.
Strong filteringConnect SPD to V−. The FPGA uses stronger digital filtering, with a maximum of 38.4 kbps.
Loading and distanceUp to 128 enhanced nodes per port. Maximum 2,200 m at 9,600 bps under suitable wiring conditions.
Isolation & Surge Protection
ItemRatingConditions
RS-485 circuits6 kV surge per portThree-stage surge protection for five channels.
Power supply input6 kV surgeProtects against transients on the supply line.
Signal and power isolation3 kVHigh-speed optocouplers and isolated DC–DC power. The five port grounds are isolated from each other and the supply ground.
AC misconnection fault220 / 380 V AC fault conditionThe isolation is intended to protect devices on other ports if a line is miswired. The affected port may be damaged.

RS-485 surge test: GB/T 17626.5 / IEC 61000-4-5, 10/700 μs open-circuit waveform and 40 Ω source impedance.

LEDs & Fault Detection
StatusPWR/D0D1–D4
Steady greenPower is on.—
Flashing greenData received at D0.Data received on that branch.
Flashing redA/B short circuit at D0.A/B short circuit on that branch.
Steady redAbnormal continuous-zero data at D0.Abnormal continuous-zero data on that branch.
OffPower is off.No received data on that branch.

Continuous-low detection compares the received low level with the maximum continuous-zero duration at 300 bps. The hub isolates the abnormal channel and lights its indicator.

Power & Environment
ItemSpecification
Supply and consumptionDC 9–70 V, under 1 W. Overload and reverse-polarity protection.
Structure and mountingFanless 35 mm DIN-rail housing, approximately 0.19 kg.
EnvironmentOperating and storage −40 to +85 °C. Operating humidity 0–95% RH, non-condensing.
ReliabilityMTBF above 200,000 hours, 100% burn-in testing and industrial Level 4 EMC per V1.5.

One PLC with four isolated field branches

Connect the PLC to D0 and the field devices to D1–D4. If branch 3 has a fault, the hub isolates it while healthy branches keep communicating.

How the hub isolates a short circuit

The diagram shows common-mode and FPGA filtering, per-channel isolation and automatic forwarding control. G1–G4 are internal. Connect each branch through its A/B pair.

Specify quantity, the DC supply, cable and mounting accessories with the order.

FCC-1210-D1D4Request a Quote
Ordering Model
Ordering ModelConfiguration
FCC-1210-D1D4One RS-485 uplink, four isolated RS-485 branches, 3 kV isolation, 6 kV surge protection and 9–70 V DC power.
Model Code
SegmentDefinition
FCC / 1210Product prefix and modular DIN-rail series.
D1One uplink on D0.
D4Four isolated RS-485 branches, D1–D4.

Wiring and port roles

2 questions
01QWhere do I connect the PLC?
A

Connect the controller to A0/B0 and its reference ground to G0. Connect field devices to the A/B pairs of D1–D4.

02QDo the four branches expose separate ground terminals?
A

The branches expose A and B. Their internal electrical grounds are isolated from the other ports and the power ground.

Filtering and faults

2 questions
03QWhen should I connect SPD to V−?
A

Use this setting for strong FPGA filtering when electrical noise affects reception. The maximum rate is 38.4 kbps in this mode and 256 kbps with SPD open.

04QWhat does a red branch LED indicate?
A

Flashing red indicates an A/B short on that branch. Steady red indicates abnormal continuous-zero data.

Power and mounting

1 question
05QWhat supply and rail does it use?
A

Connect 9–70 V DC to V+ and V− with the marked polarity. Use a 35 mm DIN rail and reserve clearance for cables.

Compare Filter Settings

Filter ModeSPD ConnectionMaximum Rate
NormalLeave SPD open256 kbps
Strong FPGA filteringConnect SPD to V−38.4 kbps