How RS485 Hubs Work: Segmentation, Termination and Polling
Check termination and polling when adding a repeater or hub to an RS-485 network.
Hub port 1 is A1/B1/G1 on the left inner row. The right inner row is port 2, and the right outer row is port 3. Connect power at V+ and V− on the left outer row. Leave NC unconnected.
Lock the rear clip onto a 35 mm DIN rail. Leave space for terminal wiring and servicing.
| Interface | Markings | Connection |
|---|---|---|
| Hub port 1 | A1 / B1 / G1 | Left inner row. Connect the shared slave in buffered mode or the master in standard hub mode. |
| Distribution port 2 | A2 / B2 / G2 | Right inner row. Connect master 1 in buffered mode or branch 1 in standard hub mode. |
| Distribution port 3 | A3 / B3 / G3 | Right outer row. Connect master 2 in buffered mode or branch 2 in standard hub mode. |
| Power and NC | V+ / V− / NC | Left outer row. DC 9–50 V with marked polarity, or AC 7–36 V per the wiring guide. Leave NC unconnected. |
| Indicators | PWR/D1, D2, D3 | Observe power and port activity on the front panel. |
Side profile: 115 × 100 mm. Front thickness: 17 mm. Approximate weight: 0.15 kg. Mounts on a 35 mm DIN rail.
| Item | Specification |
|---|---|
| RS-485 interface | Three two-wire EIA/TIA-485 channels. A (+), B (−) and independent signal ground on each port. |
| Buffering | Up to 10K bytes with frame recognition and request/reply coordination. |
| Rate and frame format | 1,200–115,200 bps, configured separately per port. Default 9,600 bps, 8N1. Select the operating mode in the configuration software. |
| Bus loading and reach | Up to 128 nodes per port and up to 2,200 m per segment at 9,600 bps. Actual distance depends on cable, speed and installation. |
| Filtering and termination | Common-mode and differential filtering. Built-in 120 Ω termination. Follow the wiring instructions for the bus topology. |
| Mode | Hub port 1 | Distribution ports 2 and 3 |
|---|---|---|
| Two masters / one slave | Shared RS-485 slave | Master 1 on port 2. Master 2 on port 3. |
| One master / two slave branches | RS-485 master | Separate slave or bus segment on each distribution port. |
| Item | Rating | Conditions |
|---|---|---|
| RS-485 channels | 6 kV surge per channel | Three-stage surge protection. |
| Power input | 6 kV surge | Overcurrent protection and DC reverse-polarity protection. |
| Port and power grounds | 3 kV isolation | Optocoupler and DC–DC isolation. G1, G2, G3 and supply ground are isolated from each other. |
| AC misconnection fault | 220 / 380 V AC fault condition | Isolation can protect equipment on the other serial ports. The affected RS-485 port may be damaged. Operating input limits are given under Power & Environment. |
RS-485 surge test: GB/T 17626.5 / IEC 61000-4-5, 10/700 μs open-circuit voltage waveform, 40 Ω source impedance.
| Item | Specification |
|---|---|
| Supply and consumption | DC 9–50 V or AC 7–36 V. Total power under 1 W. Three-position, 5.08 mm-pitch supply terminal. |
| Mounting | 35 mm DIN rail with a fanless housing. Approx. 0.15 kg. |
| Environment | −40 to +85 °C for operation and storage. 0–95% RH during operation, non-condensing. |
| Reliability | MTBF above 200,000 hours. All units are burn-in tested. Industrial Level 4 EMC per V1.2. |
Connect the two masters to ports 2 and 3 and the shared slave to port 1. The diagram shows a 24 V DC supply example.
Switch modes in the configuration software. Connect the PLC to port 1 and each RS-485 branch to its own distribution port.
Specify the desired mode, serial settings for each port, supply type and mounting accessories when ordering.
| Ordering Model | Configuration |
|---|---|
| FCC-1210-D1D2M | One hub port, two isolated RS-485 distribution ports and up to 10K bytes of buffering. DC 9–50 V / AC 7–36 V. 35 mm DIN rail. |
| Segment | Definition |
|---|---|
| FCC / 1210 | Product prefix and modular DIN-rail series. |
| D1 | One RS-485 hub port. |
| D2M | Two RS-485 distribution ports with buffering. |
In the default buffered mode, connect the masters to ports 2 and 3. Connect the shared slave to hub port 1 at A1/B1/G1.
Switch to standard hub mode in the configuration software. Connect the master to port 1 and the two field branches to ports 2 and 3.
Yes. Set baud rate and frame format independently. Each port defaults to 9,600 bps, 8N1.
G1, G2 and G3 are independent signal grounds and are mutually isolated from one another and the power ground. Follow the delivered wiring guide.
Use DC 9–50 V with marked polarity, or AC 7–36 V according to the wiring guide. Leave NC open.
Check termination and polling when adding a repeater or hub to an RS-485 network.