Industrial 35mm Rail AC220V to DC12V2A-24V1A Power Supply FCW-24-1
- View : 1,674
- Share :
- Model : FCP-1202
- Description :
● 35mm rail housing;
● 2 power supply specifications: 12V2A/24V1A, full power output, small temperature rise.
● Designed according to safety regulations, isolation withstand voltage greater than 1500Vac.
● Designed with reference to EMC requirements, strong anti-interference ability.
● Complete protection functions: output overcurrent, overload, short circuit protection.
● Can resist inductive high voltage, surge protection, etc.;
● Fanless, efficient and thick heat dissipation aluminum alloy heat dissipation, reducing repair time;
● Wide temperature type: working temperature -40℃~ +65℃;
● Full load high temperature burn-in, 100% aging test;
|
Parameter |
Model |
FCP-1202 |
FCP-2401 |
|
Output
|
Voltage |
12V |
24V |
|
Current |
0-2A |
0-1A |
|
|
Rated Power |
24W |
24W |
|
|
Voltage Ripple (noise) |
25mVp-p |
38mVp-p |
|
|
Voltage Accuracy |
±3% |
±3% |
|
|
Line Regulation |
±0.3% |
±0.3% |
|
|
Load Regulation |
±1% |
±1% |
|
|
Work Efficiency |
>=88% |
>=90.7% |
|
|
Start-up & Rise Time |
1500ms,30ms/220Vac;2500ms,50mS/110Vac(At full load) |
||
|
Input
|
Voltage Range |
90vc–264Vac;127VDC–370VDC |
|
|
Alternating Current |
0.5A/220 volt,1A/110 volt |
||
|
Frequency Range |
47-63Hz |
||
|
Lightning Strikes & Surge |
6KV lightning protection, surge current: cold start <40A/230VAC |
||
|
Protect
|
Output Short Circuit |
Hiccup mode, output can be automatically restored after fault is cleared |
|
|
Output Over Current |
Rated output current 130%-200% |
||
|
Output Overload |
Rated output power 130%-200% |
||
|
Environment
|
Operating Temperature |
-30℃—+65℃ |
|
|
Working Humidity |
20-90% RH (No condensation) |
||
|
Storage Temperature |
-40℃—+85℃ |
||
|
Storage Humidity |
10-95% Relative humidity |
||
|
Vibration |
10-500Hz, 2G 10min/cycle, 60min each for X, Y and Z axis |
||
|
MTBF |
>100,000 hours |
||
|
Dimensions (L x W x H) |
90mm*22.5mm*100mm |
|
Weight |
0.23kg |
Remark:
1. Unless otherwise specified, all specifications and parameters are measured at 220Vac input, rated load, and 25℃ ambient temperature.
2. Voltage noise measurement method: Use 30cm double-stripe wire to connect 1 0.1uF and 1 47uF capacitor in parallel, and measure with a bandwidth of 20MHz.
3. Accuracy: includes setting error, linear adjustment rate and load regulation.
4. Linear regulation rate measurement method: Under the condition of rated output power, adjust the input voltage within the full range and measure the output voltage change rate.
5. Load regulation rate measurement method: Measure the output voltage change rate when the output current is adjusted within the full range.
Tell us what you need. We can help with product selection and a quotation.