Industrial Rail AC220V to DC12V2A-24V1A-12V4A-24V2A Power Supply FCW-26-1
- View : 1,583
- Share :
- Model : FCP-1202G
- Description :
● IP40 protection level, thick heat dissipation aluminum alloy anodized process shell, can withstand the test of harsh environment;
● With digital tube to display voltage, it is convenient for on-site voltage adjustment and business operation.
● 4 power supply specifications: 12V2A/24V1A/12V4A/24V2A full power output, small temperature rise.
● Designed according to safety regulations, isolation withstand voltage greater than 1500Vac.
● Designed with reference to EMC requirements, strong anti-interference ability.
● Complete protection functions: output overcurrent, overload, short circuit protection.
● Lightning protection function, 6KV lightning protection, can resist inductive high voltage, surge protection, etc.;
● Fanless and efficient thick heat dissipation aluminum alloy heat dissipation, reducing repair time;
● IP40 shell protection level, can withstand the test of harsh environment;
● DIN 35mm rail or wall-mounted installation;
● Wide temperature type: working temperature -40℃~ +85℃;
● Full load high temperature burn-in, 100% aging test;
|
Parameter |
Model |
FCP-1202G |
FCP-2401G |
FCP-1204G |
FCP-2402G |
|
Output
|
Voltage |
12V |
24V |
12V |
24V |
|
Current |
0-2A |
0-1A |
0-4A |
0-2A |
|
|
Rated Power |
24W |
24W |
48W |
48W |
|
|
Voltage Ripple (noise) |
25mVp-p |
38mVp-p |
25mVp-p |
38mVp-p |
|
|
Voltage Accuracy |
±3% |
±3% |
±3% |
±3% |
|
|
Line Regulation |
±0.3% |
±0.3% |
±0.3% |
±0.3% |
|
|
Load Regulation |
±1% |
±1% |
±1% |
±1% |
|
|
Work Efficiency |
>=88% |
>=90.7% |
>=88% |
>=90.7% |
|
|
Start-up & Rise Time |
1500ms,30ms/220Vac;2500ms,50mS/110Vac(At full load) |
||||
|
Input
|
Voltage Range |
90vc–264Vac;127VDC–370VDC |
|||
|
Alternating Current |
0.5A/220 volt,1A/110 volt |
||||
|
Frequency Range |
47-63Hz |
||||
|
Lightning Strikes & Surge |
6KV lightning protection, surge current: cold start <40A/230VAC |
||||
|
Protect
|
Output Short Circuit |
Hiccup mode, output can be automatically restored after fault is cleared |
|||
|
Output Over Current |
Rated output current 130%-200% |
||||
|
Output Overload |
Rated output power 130%-200% |
||||
|
Environment
|
Operating Temperature |
-40℃—+85℃ |
|||
|
Working Humidity |
20-90% RH (No condensation) |
||||
|
Storage Temperature |
-40℃—+85℃ |
||||
|
Storage Humidity |
10-95% Relative humidity |
||||
|
Vibration |
10-500Hz, 2G 10min/cycle, 60min each for X, Y and Z axis |
||||
|
MTBF |
>100,000 hours |
||||
|
Dimensions (L x W x H) |
110mm*81.1mm*45mm |
|
Weight |
0.56kg |
Remark:
1. Unless otherwise specified, all specifications and parameters are measured at 220Vac input, rated load, and 25℃ ambient temperature.
2. Voltage noise measurement method: Use 30cm double-stripe wire to connect 1 0.1uF and 1 47uF capacitor in parallel, and measure with a bandwidth of 20MHz.
3. Accuracy: includes setting error, linear adjustment rate and load regulation.
4. Linear regulation rate measurement method: Under the condition of rated output power, adjust the input voltage within the full range and measure the output voltage change rate.
5. Load regulation rate measurement method: Measure the output voltage change rate when the output current is adjusted within the full range.

Tell us what you need. We can help with product selection and a quotation.