+8618758069661 [email protected]

16-Port RS-485 DIN-Rail Isolated Hub

Model:FCC-1600-D1D16
1,410 +0

Give 16 RS-485 branches independent connections

  • Connect one controller to 16 isolated branchesPort 0 is the RS-485 uplink on the D1 model. Active branch ports 1–16 have independent reference grounds.
  • Match the uplink at orderingChoose FCC-1600-D1D16 for RS-485 or FCC-1600-R1D16 for RS-232. Both versions have 16 RS-485 branches.
  • Filter line interference and use redundant DC powerFPGA filtering is configurable. Dual 9–70 V DC inputs support redundant power.

Purpose & Applications

  • Expand a PLC or host serial connection to 16 isolated RS-485 branches for field devices and instruments.
  • Forward Modbus RTU and other serial data transparently. Select the RS-485 or RS-232 uplink when ordering.
  • Keep each branch reference ground separate from all other reference grounds and from power ground to retain 2.5 kV isolation.

Key Features

16 active branches
Ports 1–16 each have an independent RS-485 transceiver. Positions 17 and 18 are reserved.
Filtering and direction
Common-mode and differential filtering plus optional FPGA digital filtering. Automatic transmit enable.
Isolation and surge protection
2.5 kV isolation and 6 kV surge protection per RS-485 channel.
Power and installation
Dual redundant 9–70 V DC. Fanless IP40 anodized aluminum housing with DIN-rail or wall mounting.

Terminal Groups
InterfaceMarkingsConnection
Uplink Port 0Three-pin terminalD1 RS-485: 1=A, 2=B, 3=GND. R1 RS-232: RXD, TXD and GND. Follow the delivered wiring order for the R1 model.
Branches 1–161=A (TX+), 2=B (TX−), 3=GNDConnect the twisted pair to A/B. Keep the shield/reference ground independent for each branch.
Positions 17 and 18ReservedConnect field devices to active ports 1–16 only.
Dual DC inputV2−, V2+, V1−, V1+Left to right, PWR2 then PWR1. Apply 9–70 V DC with correct polarity.
DIP Switch & Digital Filtering
SwitchPositionResult
DIP-1OFF (default)Digital filtering off. Maximum 200 kbps.
DIP-1ONDigital filtering enabled. Up to 38,400 bps.
DIP-2 to DIP-4ReservedLeave in the delivered position.
Dimensions & Mounting

164 × 132 × 50 mm (L × W × H), approximately 1.15 kg. Rail or wall mounting.

Communication & Filtering
ItemSpecification
Uplink standardsRS-485 on FCC-1600-D1D16, EIA/TIA-485. RS-232 on FCC-1600-R1D16, EIA/TIA-232 (ITU-T V.28).
Branches and forwarding16 independently isolated RS-485 channels. Transparent protocol-independent forwarding, automatic transmit enable and per-channel transmit indicators.
Rate and loadingUp to 200 kbps with filtering disabled. Higher rates require factory confirmation. Each channel supports at least 32 standard nodes or up to 128 enhanced nodes.
FilteringCommon-mode inductor and differential filtering, plus selectable FPGA digital filtering. Up to 38,400 bps with digital filtering enabled.
Port Protection & Isolation
ItemRatingConditions
RS-485 branches6 kV surge per channelIndependent protection against induced and switching transients.
RS-232 uplink and DC input6 kV surgeApplies to the RS-232 uplink configuration and the supply input.
Signal and ground isolation2.5 kVOptical signal isolation and separate branch shield/reference grounds. Power ground is isolated from all 16 RS-485 branches.
AC misconnection test220 / 380 V ACFault isolation can protect devices across the barrier. The misconnected port may be damaged.
Power, Enclosure & Environment
ItemSpecification
PowerDual redundant 9–70 V DC, isolated, <10 W. Overload and reverse-polarity protection. Four-pin 5.08 mm pluggable block.
Mounting and enclosureFanless IP40 anodized aluminum, DIN rail or wall. 164 × 132 × 50 mm, approximately 1.15 kg.
EnvironmentOperating and storage −40 to +85 °C. Operating humidity 0–95% RH, non-condensing.
ReliabilityMTBF >100,000 hours, 100% burn-in tested and industrial Level 4 EMC per datasheet.

Connect a PLC to 16 field instruments

The D1 example connects the PLC to Port 0 and one instrument to each active branch. Ports 3–14 are represented by an ellipsis. Use A/B for each twisted pair and the corresponding isolated GND.

Choose the Port 0 Uplink Standard

Both versions include 16 RS-485 branches. Specify the baud rate and mounting accessories when ordering. Higher-speed versions require factory confirmation.

FCC-1600-D1D16Request a Quote
Ordering Models
Ordering ModelConfiguration
FCC-1600-D1D16RS-485 uplink, 16 isolated RS-485 branches
FCC-1600-R1D16RS-232 uplink, 16 isolated RS-485 branches

Ports and wiring

2 questions
01QAre positions 17 and 18 active?
A

Use active branches 1–16. Positions 17 and 18 are reserved.

02QWhat is the pin order for each RS-485 branch?
A

Pin 1 is A (TX+), Pin 2 is B (TX−) and Pin 3 is the branch GND. Keep branch reference grounds separate.

Uplink and filtering

2 questions
03QWhat is the difference between D1D16 and R1D16?
A

D1D16 uses RS-485 at Port 0. R1D16 uses RS-232 at Port 0. Both have 16 RS-485 branches.

04QDoes DIP-1 affect the highest baud rate?
A

DIP-1 OFF allows up to 200 kbps. DIP-1 ON enables digital filtering and allows up to 38,400 bps.

Power and mounting

1 question
05QWhich supply and mounting options can I use?
A

Use redundant 9–70 V DC on the marked PWR2 and PWR1 inputs. The enclosure supports rail or wall mounting.

Compare Uplink Options

Ordering ModelConfiguration
FCC-1600-D1D16RS-485 uplink, 16 isolated RS-485 branches
FCC-1600-R1D16RS-232 uplink, 16 isolated RS-485 branches

Send a product inquiry

Tell us your application, quantity and preferred configuration.

We use your information only to respond to this inquiry.